Depending on the selected verbosity level additional parameters are logged: the
protective field number, the sensor which detected the motion.
Format:
Detection exit (field #n)
Example:
20 2020/11/18 16:47:25 [INFO] CONTROL Detection exit (field #1)
8.3.8
Dynamic configuration in use
At every change of the dynamic configuration, the new ID of the dynamic configuration
selected is logged.
Format:
Dynamic configuration #1
Example:
20 2020/11/18 16:47:25 [INFO] CONTROL Dynamic configuration #1
8.3.9
Muting status
Every change of the muting status of each sensor is logged as disabled or enabled.
Note
: the event indicates a change of the muting status of the system. It does not
correspond to the muting request.
Format:
Muting disabled/enabled
Example:
20 2020/11/18 16:47:25 [INFO] SENSOR#1 Muting enabled
8.3.10
Fieldbus connection
The Fieldbus communication status is logged as CONNECTED, DISCONNECTED or
FAULT.
Format:
Fieldbus connection CONNECTED/DISCONNECTED/FAULT
Example:
20 2020/11/18 16:47:25 [INFO] CONTROL Fieldbus connection CONNECTED
8.3.11
Modbus connection
The Modbus communication status is logged as CONNECTED or DISCONNECTED.
Format:
Modbus connection CONNECTED/DISCONNECTED
8 MAINTENANCE AND TROUBLESHOOTING
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3