LED
Status
Meaning
F3 (link)
Off
Data exchange is running with the host
Flashing red
No data exchange
Steady red
No physical link
F4 (not used)
-
-
F5 (diagnosis)
Off
Normal behavior
Flashing red
DCP signal service is initiated via the bus
Steady red
diagnostic error at PROFIsafe layer (wrong F Dest Address,
watchdog timeout, wrong CRC) or diagnostic error at
PROFINET layer (watchdog timeout; channel, generic or
extended diagnosis present; system error)
F6 (not used)
-
-
4.2.6
Inputs
The system has two type 3 digital inputs (according to IEC/EN 61131-2). Each digital
input is dual channel, and the ground reference is common for all the inputs (see
Technical references on page 96
).
When using digital inputs, it is mandatory that the additional SNS input "V+ (SNS)" is
connected to 24 V DC and that the GND input "V- (SNS)" is connected to the ground in
order to:
l
perform the correct input diagnostic
l
assure the system safety level
The function of each digital input must be programmed through the safeRS3 Designer
application. The available functions are the following:
l
Stop signal
: optional safety function, manages a specific signal to force all the
safety outputs (detection signals, if present) to OFF-state.
l
Restart signal
: optional safety function, manages a specific signal which enables
the control to switch to ON-state the safety outputs related to all the protective fields
with no motion detected.
l
Muting group “N”
: optional safety function, manages a specific signal which allows
the control to ignore the information coming from a selected group of sensors.
l
Activate dynamic configuration
: allows the control to select a specific dynamic
configuration.
l
Fieldbus controlled
(if available): monitors the input status through Fieldbus
communication. For example, a generic ESPE can be connected to the input,
respecting electrical specifications.
For details about digital input signals, see
Digital input signals on page 114
.
4.2.7
Input variable behavior
If neither digital input nor OSSD is configured as
Fieldbus controlled
, the behavior of
the input variables is as described below:
4 GET TO KNOW SAFERS3
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3
23