Ethernet gateways
How to change the start address for the data sets:
Open the Flexi Soft Designer and load the hardware configuration including the
EtherCAT gateway. Ensure your project is offline.
Click on the
Gateways
button above the main window and select the FX0-GETC or
double click the FX0-GETC in the hardware configuration view to open the gateway
configuration dialog.
Click on
Gateway configuration
on the left hand menu. The following dialog appears:
Click on the button to the right of the data set for which you want to change the start
address. The following dialog appears:
Type in the desired new start address or use the arrows to change the address. The
address will be checked automatically for plausibility, i.e. it is not possible to configure
data sets with overlapping address ranges.
Click
OK
to accept the new start address.
Fig. 51: EtherCAT gateway
configuration dialog
Fig. 52: Edit the data block
start address