Operating Instructions
Chapter
8
Flexi Soft Gateways
8012664/XB29/2013-06-11
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
183
Subject to change without notice
Technical specifications
8
Technical specifications
8.1
Technical specifications gateways
8.1.1
EtherNet/IP, Modbus TCP, PROFINET IO
Interface
Fieldbus
EtherNet/IP, Modbus TCP, PROFINET IO
Integrated switch
3-port layer-2 managed switch with Auto-
MDI-X for automatic detection of crossed
Ethernet cable
Connection technique
RJ-45 socket
Transfer rate
10 Mbit/s (10 Base-T) or 100 Mbit/s (100
Base-TX), autosensing
Update rate (heartbeat rate)
Configurable from 40 … 65,535 ms
Change of state (COS) update rate
10 ms
Addressing factory setting
IP: 192.168.250.250
Subnet mask: 255.255.0.0
Default gateway: 0.0.0.0
MAC address
Printed on type label, example:
00:06:77:02:00:A7
8.1.2
EtherCAT
Interface
Fieldbus EtherCAT
Connection technique
RJ-45 socket
EtherCAT application cycle time
4 ms
Watchdog Time Process Data
O
5 ms
Watchdog Time Process Data Interface
(PDI)
O
55 ms
Tab. 150: Technical specifi-
cations FX0-GENT, FX0-
GMOD and FX0-GPNT
Tab. 151: Technical
specifications FX0-GETC