Product description Flexi Soft
gateways
The second relevant byte is the module status byte 3 for module 2. This is byte 08 with the
hex value EF (11101111):
Bit #
7
6
5
4
3
2
1
0
Value
1
1
1
0
1
1
1
1
This corresponds to the error message “Short-circuit monitoring output 3, short-circuit to
high” (byte 3, bit 4 in Tab. 9).
You will find an example process image in section 5.1.3 “TCP/IP process image example”
on page 46.
Tab. 16: Example module
status byte 3 of module 2