Chapter
6
Operating Instructions
Flexi Soft Gateways
130
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8012664/XB29/2013-06-11
Subject to change without notice
Fieldbus gateways
6.2
CANopen gateway
The following Flexi Soft gateway can be used for CANopen: FX0-GCAN.
6.2.1
Interfaces and operation
Controls and status indicators
LED
Meaning
No power supply
Green
Operational, power supply switched on
P
W
R
(P
ow
er
)
Red System
error
CANopen status: Stopped (except node guarding and
heartbeat, if active)
Green
CANopen status: Operational (PDO + SDO data exchange)
Green
CANopen status: Pre-operational (SDO data exchange only)
Red
CAN bus off (hardware problem CAN physical layer) or
Error passive
N
S
(N
et
w
or
k
S
ta
tu
s)
Red (1 Hz)
Node guarding failed (NMT master does not monitor slave
anymore) or Heartbeat consumer failure
Power-up
Green
Executing, and PDO status: all “Good”
Green
Idle (cable not attached or node guarding failed)
Red/green
Executing, and PDO status: any is “Bad”
Red
Critical fault, caused by emergency bit
Red (1 Hz)
Configuration required or in progress
M
S
(M
od
ul
e
S
ta
tu
s)
Red (2 Hz)
Critical fault, caused by gateway itself
For diagnostics see section 6.2.14 “Diagnostics and troubleshooting” on page 159.
Fig. 64: Controls and status
indicators FX0-GCAN
Tab. 94: Meaning of the
status LEDs of the FX0-GCAN
Symbol description:
: LED is off
Green: LED lights up green
Red: LED flashes red
Address switch 2
Baud rate DIP switch
CANopen connection
Address switch 1
Power LED (green)
Module status LED
(red/green)
Network status LED
(red/green)