Operating Instructions
Chapter
6
Flexi Soft Gateways
8012664/XB29/2013-06-11
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
125
Subject to change without notice
Fieldbus gateways
The following table matches the module specific diagnostics data (as defined by the GSD)
to the appropriate error message.
The module status bits have the following significance, if not otherwise stated:
0 = Error
1 = No error
Module
number
[dec]
Diagnostics bit
[Octet Bit]
Error origin Error message
12.0
Operating state Run
12.1
Internal tests
12.2
Summary of bits 12.5 to 12.7
12.3
Reserved
12.4
Configuration Flexi Soft system
12.5
Power supply
12.6
EFI1
12.7
EFI2
13.0
Flexi Link stations in the system
1 = All found
0 = One or more are missing
13.1
Flexi Link stations suspended
1 = None
0 = One or more
1
13.2 … 15.7
CPU
Reserved
12.0
Operating state Run
12.1
Internal tests
12.2
Summary of bits 12.5 to 12.7
12.3
Reserved
12.4
Configuration of this module is valid
12.5
Outputs power supply
12.6
Output
Fast-Shut-Off
12.7
Reserved
13.0
Input 1-2 dual channel input evaluation
13.1
Input 3-4 dual channel input evaluation
13.2
Input 5-6 dual channel input evaluation
13.3
Input 7-8 dual channel input evaluation
13.4 … 13.7
Reserved
14.0
External test signal Input 1
14.1
External test signal Input 2
14.2
External test signal Input 3
14.3
External test signal Input 4
14.4
External test signal Input 5
14.5
External test signal Input 6
14.6
External test signal Input 7
14.7
External test signal Input 8
15.0
Short-circuit monitoring output 1: short-circuit to high
15.1
Short-circuit monitoring output 1: short-circuit to low
15.2
Short-circuit monitoring output 2: short-circuit to high
15.3
Short-circuit monitoring output 2: short-circuit to low
15.4
Short-circuit monitoring output 3: short-circuit to high
15.5
Short-circuit monitoring output 3: short-circuit to low
15.6
Short-circuit monitoring output 4: short-circuit to high
2
15.7
XTIO/XTDI
Short-circuit monitoring output 4: short-circuit to low
12.0
Operating state Run
12.1
Internal tests
12.2
Summary of bits 12.5 to 12.7
12.3
Reserved
12.4
Configuration of this module is valid
12.5
Communication from the network
12.6
Communication to the network
3
12.7 … 15.7
PROFIBUS
gateway
Reserved
Tab. 92: PROFIBUS error
messages