Operating Instructions
Chapter
5
Flexi Soft Gateways
8012664/XB29/2013-06-11
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
47
Subject to change without notice
Ethernet gateways
Byte values [hex] Part of message
Meaning
52 A1 10 4C
Overall CRC (same as system CRC)
52 A1 10 4C
System CRC
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
Data set 2
(see Tab. 5)
Reserved
FF FF FF FF
Status module 0 (FX3-CPUx): OK
FF FF FF FF
Status module 1 (e.g. FX3-XTDI): OK
FD FB FF FF
Status module 2 (e.g. FX3-XTIO):
Byte 0: FF = 11111111: No errors
Byte 1: FF = 11111111: No errors
Byte 2: FB = 11111011: Input 3 external
test signal failure.
Byte 3: FD = 11111101: Output 1
stuck
R
at
R
low error
FF FF FF FF
FF FF FF FF
FF FF FF FF
FF FF FF FF
Status modules 3-6: OK
FF FF FF FF
FF FF FF FF
FF FF FF FF
FF FF FF FF
FF FF FF FF
FF FF FF FF
Status modules 7-12 (no modules present)
FF FF FF FF
Status module 13 (e.g. FX0-GENT): OK
FF FF FF FF
Data set 3
(see Tab. 5 and section
3.3.6 “Error and status
information of the
modules” on page 19)
Data set 3 data is
transferred in Big Endian
format, i.e. in 32 bit
double word format with
the most significant byte
placed in the leftmost
position.
Status module 14 (no module present)
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
00 00 00 00
Data set 4
Reserved