MOUNTING
4
55
8020776/12AX / 2019-05-31|SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S |Free Flow Profiler
4.2
Mounting the Traffic Controller FPS
WARNING
Consider the protection class
▸
The Traffic Controller FPS has an IP 20 protection class rating and must always be
mounted in an electric or control cabinet.
NOTE
The Traffic Controller FPS must not be opened. The hard drive is already integrated into
the device.
The Traffic Controller FPS should be mounted in a suitable location inside the control
cabinet at the measurement site.
Ideally, it should be mounted near the higher-level control but never in the vicinity of
transformers or other power units.
In order to accommodate the leads and wiring, there must be enough terminals available.
Mounting
▸
Install the Traffic Controller FPS in a suitable location inside the control cabinet.
To do this, use the M4 thread in the Traffic Controller FPS.
The Traffic Controller FPS does not have active cooling. For optimum heat dissipation
inside the control cabinet, we recommend mounting it on a metal plate.
4.3
Mounting the Ethernet switch
The profiling system requires an Ethernet switch with at least
4 ports
.
▸
Mount the Ethernet switch in a suitable location inside the control cabinet.
Note