- 15 -
(2) Battery Charge Monitor Lamp
The battery charge monitor lamp ("CHARGE") lights up and the engine is
automatically stopped if battery charge fails during operation. If this occurs, it is
probable that there is fan belt damage or a wiring fault. Request repair at the retail
outlet where the equipment was purchased.
(3) Oil Pressure Monitor Lamp
The oil pressure monitor lamp ("OIL PRESS") lights up and the engine is
automatically stopped if the engine oil pressure drops during operation. If this
occurs, inspect the engine oil level and fill with engine oil until it reaches the
maximum level.
<<<<
Note
>>>>
•
The oil pressure monitor cannot detect oil deterioration. Change the engine oil
periodically.
(
Refer to section "11
.
(1) Changing the Engine Oil" .
)
•
The charge monitor cannot detect battery deterioration or insufficient battery fluid.
Inspect the battery fluid level periodically.
(
Refer to section "6-6
.
Battery
Inspection" .
)
•
Inspect the fuses if the engine is automatically stopped and none of the monitor
lamps ("WATER TEMP", "CHARGE" and "OIL PRESS") light up.
(
Refer to section
"4
.
Part Names" for fuse location.
)
If a fuse has blown, it is probable that there is a fault in an electric part or the
wiring. Request repair at the retail outlet where the equipment was purchased.
(4) Spill Containment Monitor Lamp
The spill containment monitor lamp ( "SPILL CONTAINMENT" ) lights up if the level
of liquid in the spill containment is approximately 70% full (approx. 36 L) in order to
ensure that liquid accumulated in the spill containment does not spill out of the
equipment. If this occurs, drain the accumulated liquid from the equipment.
(
Refer
to section "11. (7) Draining Liquid from the Spill Containment" .
)
<<<<
Note
>>>>
•
The engine is not stopped if the spill containment monitor lamp lights up during
operation.
•
When the spill containment monitor lamp lights up during operation, stop the
engine, check for fuel, oil and cooling water leakage, and repair as necessary.
•
Do not use the equipment with liquid accumulated in the spill containment. Drain
the spill containment before using.
(
Refer to section "11. (7) Draining Liquid from
the Spill Containment" .
)
5-9
.
.
.
.
Frequency Selector
Warning: Injury/Electric Shock
•
Do not operate the equipment with any doors or covers open. There is a
danger of hair, body parts and other items being caught up in moving
parts such as cooling fans and belts.