7
Startup
Startup procedure
Manual – PROFINET IO Interfaces, Field Distributors
81
6. Set the maximum speed using setpoint potentiometers f1 of all MOVIMOT
®
invert-
ers.
100
[1]
2
1
0
2
3
4
5
6
7
8
9 10
75
25
50
6
5
f1
f1
Hz
27021598093635979
[1]
Potentiometer setting
7.
NOTICE!
Loss of warranted degree of protection if the screw plugs of the f1 set-
point potentiometer or the X50 diagnostic interface are installed incorrectly or not
at all. Damage to the MOVIMOT
®
inverter.
Make sure all screw plugs have a seal and screw it in.
8. Set the minimum frequency f
min
using the switches f2 on all MOVIMOT
®
inverters.
3
4
5
6
7
8
Function
Setting
Detent setting
0
1
2
3
4
5
6
7
8
9
10
Minimum frequency f
min
/Hz
2
5
7
10
12
15
20
25
30
35
40
9. If the ramp time is not specified via fieldbus (2 PD), set the ramp time at the t1
switches of all MOVIMOT
®
inverters.
ð
The ramp time is based on a setpoint step change of 1500 min
-1
(50 Hz).
3
4
5
6
7
8
Function
Setting
Detent setting
0
1
2
3
4
5
6
7
8
9
10
Ramp time t1/s
0.1 0.2 0.3 0.5 0.7
1
2
3
5
7
10
10. Check to see if the requested direction of rotation has been enabled on all
MOVIMOT
®
inverters.
CW/stop
CCW/stop
Meaning
Activated
Activated
•
Both directions of rotation are enabled.
24V
L
R
Activated
Not activated •
Only CW rotation is enabled.
•
Setpoint selection for CCW rotation will stop the
drive.
L
R
24V
Not activated
Activated
•
Only CCW rotation is enabled
•
Setpoint selection for CW rotation will stop the
drive.
L
R
24V
22870857/EN – 12/2016