12
MOVILINK
®
device profile
Coding of the process data
Manual – PROFINET IO Interfaces, Field Distributors
145
Speed [%]
The speed setpoint is given as a relative value in percentage and refers to maximum
speed set using the setpoint potentiometer f1.
Coding:
C000
hex
= -100% (counterclockwise rotation)
4000
hex
= +100% (clockwise rotation)
→ 1 digit = 0.0061%
Example:
80% f
max
, CCW rotation:
Calculation:
-80% / 0.0061 = -13115
dec
= CCC5
hex
Ramp
The current integrator in the process output data word PO3 is transferred if the pro-
cess data exchange takes place using three process data words. The integrator ramp
set with switch t1 is used if the MOVIMOT
®
drive is controlled using 2 process data
words.
Coding:
1 digit = 1 ms
Range:
100 – 10000 ms
Example:
2.0 s = 2000 ms = 2000
dec
= 07D0
hex