PROFINET IO configuration
PROFINET IO configuration with topology detection
Manual – PROFINET IO Interfaces, Field Distributors
106
8.7.5
PROFINET topology – diagnostics
Topology errors are reported to the PROFINET IO controller as diagnostics alarms.
The "Network view" shows the connection errors in form of a red cross [1].
[1]
19272451595
Possible causes:
•
Ethernet ports swapped
•
Incorrectly set port properties
•
Devices cannot be addressed
Proceed as follows to display information about an error:
1. Select the device or the respective slot.
2. Right-click and select "Module status" from the context menu.
ð
A window is displayed.
3. Select the "Communication diagnostics" tab.