11
Supplementary field distributor startup information
MOVIMOT® inverter integrated in field distributor
Manual – PROFINET IO Interfaces, Field Distributors
142
11.5.2
Additional functions for MOVIMOT
®
integrated in the field distributor
The following additional functions are available when MOVIMOT
®
is integrated in the
Z.7., Z.8. or Z.9. field distributor (to a limited extent). A detailed description of the addi-
tional functions can be found in the MOVIMOT
®
operating instructions.
Additional function
Restriction
1
MOVIMOT
®
with increased ramp times
–
2
MOVIMOT
®
with adjustable current limiting
(fault if limit is exceeded)
–
3
MOVIMOT
®
with adjustable current limiting
(switchable using terminal f1/f2)
Not available
4
MOVIMOT
®
with bus configuration
Not available
5
MOVIMOT
®
with motor protection in Z.7., Z.8.
or Z.9. field distributor
–
6
MOVIMOT
®
with maximum 8 kHz PWM fre-
quency
–
7
MOVIMOT
®
with rapid start/stop
The mechanical brake can
only be controlled by
MOVIMOT
®
.
It is not possible
to control the brake using
the relay output.
8
MOVIMOT
®
with minimum frequency 0 Hz
–
10
MOVIMOT
®
with minimum frequency 0 Hz and
reduced torque at low frequencies
–
11
Monitoring of line phase failure deactivated
–
12
MOVIMOT
®
with rapid start/stop and motor pro-
tection in Z.7., Z.8. or Z.9. field distributors
The mechanical brake can
only be controlled by
MOVIMOT
®
.
It is not possible
to control the brake using
the relay output.
14
MOVIMOT
®
with deactivated slip compensation –
INFORMATION
Do not use additional function 9 "MOVIMOT
®
for lifting applications" and additional
function 13 "MOVIMOT
®
for lifting applications with extended n-monitoring" when the
MOVIMOT
®
inverter is integrated in the Z.7., Z.8. and Z.9. field distributor.
22870857/EN – 12/2016