Cable routing and cable shielding
Electrical Installation
5.5
Cable routing and cable shielding
5.5.1
Notes on cable routing and cable shielding
Note the following when routing and shielding the cables:
• Cable selection
– You can use unshielded connection cables for the supply system leads
(3 x AC 400 V – AC 500 V + PE).
– Control cables must be shielded. Route them separately from cables that emit
interference (e.g. control cables of solenoid valves, motor leads).
– The shield must have good EMC properties (high shield attenuation) and must not
be used for mechanical protection of the cable.
• Cable shielding
– The AS-Interface data cable and sensors are generally connected via plug
connectors.
– Connect the cable shields of the control cables to the metal housing of the unit via
EMC cable glands.
5.5.2
Recommended cable routing
The following figure shows the recommended cable routing:
2661020811