Operating Instructions – MOVIGEAR® DAC-B
127
8
Description of command pcb parameters
Parameters
Ramp t15 up index
10504.1
Only in conjunction with AS-Interface double slave GLK31A:
Use this parameter to set acceleration ramp "t15 up" (depending on which function
module is active).
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
Ramp t15 down
index 10504.11
Only in conjunction with AS-Interface double slave GLK31A:
Use this parameter to set deceleration ramp "t15 down" (depending on which function
module is active).
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
Ramp t16 up index
10475.2
Only in conjunction with AS-Interface double slave GLK31A:
Use this parameter to set acceleration ramp "t16 up" (depending on which function
module is active).
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
Ramp t16 down
index 10475.1
Only in conjunction with AS-Interface double slave GLK31A:
Use this parameter to set deceleration ramp "t16 down" (depending on which function
module is active).
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
Command pcb parameters \ setpoints/ramp generators \ setpoints
Setpoint n_f1
index 10096.35
Use this parameter to set setpoint "n_f1".
• Unit: [rpm]
• Setting range: 0 – 1500 – 2000 rpm
The setpoint "n_f1" is valid if
• setpoint potentiometer f1 is deactivated, i.e. when parameter 10096.30, bit 13 = "1"
• parameter 10096.34 terminal configuration = "0"
• the signal "0" is present at terminal f1 / f2.