![SEW-Eurodrive MOVIGEAR DAC B Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/sew-eurodrive/movigear-dac-b/movigear-dac-b_operating-instructions-manual_1250343060.webp)
60
Operating Instructions – MOVIGEAR® DAC-B
5
Terminal assignment
Electrical Installation
5.3
Terminal assignment
The following figure shows the terminal assignment of MOVIGEAR
®
DAC:
DANGER
The drive is operated as a generator when the hollow shaft is turned.
Severe or fatal injuries from electric shock.
• Secure the output shaft against rotation when the electronics cover is removed.
2370851211
Assignment
Terminal
No.
Name
Color
Function (permitted tightening torque)
Supply
system
terminals
–
L1
Brown
Line connection phase L1 (1.2 to 1.4 Nm)
–
L2
Black
Line connection phase L2 (1.2 to 1.4 Nm)
–
L3
Gray
Line connection phase L3 (1.2 to 1.4 Nm)
–
PE
–
Protective earth connection (2.0 to 3.3 Nm )
Control
terminals
1
STO+
Yellow
Input STO+
2
STO
−
Yellow
Input STO –
3
K1a
–
Signal relay
4
DI01
–
Binary input DI01
5
DI03
–
Binary input DI03
6
24V_O
–
DC 24 V output
7
0V24_O
–
0V24 reference potential output
11
STO+
Yellow
Output STO + (to loop through)
12
STO
−
Yellow
Output STO – (to loop through)
13
K1b
–
Signal relay
14
DI02
–
Binary input DI02
15
DI04
–
Binary input DI04
16
24V_O
–
DC 24 V output
17
0V24_O
–
0V24 reference potential output
PE
PE
L1
L2
L3
PE
PE
1
11 12 13 14 15 16 17
2
3
4
5
6
7
AS+
AS−
DI2
DI3
V024
V024
V0
V0
Содержание MOVIGEAR DAC B
Страница 2: ...SEW EURODRIVE Driving the world...
Страница 257: ......