SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
175
Technical data
11
11.1
Technical data
Device configuration
●
2 slots for up to 2 optional expansion modules
●
2 opto-isolated digital inputs with one shared terminal
●
2 opto-isolated digital outputs with one shared terminal
●
1 Ethernet interface, RJ45 socket for connecting to the PC or network
Measurement
Only for connection to AC voltage systems
Measuring method
For voltage measurement
TRMS value measurement up to the 63rd harmonic
for current measurement
TRMS value measurement up to the 63rd harmonic
Measured value acquisition
Energy
Contiguous (zero blind measuring)
Current, voltage
Contiguous (zero blind measuring)
Settable refresh time for values on the display: 330 to
3000 ms
Waveform
Sinusoidal or distorted
Frequency of the relative fundamental
50 / 60 Hz
Measured value acquisition mode
Automatic mains frequency acquisition
Measuring inputs for voltage
Device with wide-voltage power supply
Voltage ph-n
Voltage ph-ph
3~ 400 V AC (+ 20 %), max. 347 V for UL
3~ 690 V AC (+ 20 %), max. 600 V for UL
Min. measurable voltage
Voltage ph-n
AC 3~ 57 V – 80%
Voltage ph-ph
AC 3~ 100 V – 80%
Impulse withstand voltage
> 9.5 kV (1.2/50 μs)
Measuring category
(in accordance with IEC/UL 61010 Part 1)
Input voltage V
I
CAT III
Input resistance (ph-n)
1.05 Mohms
Power consumption per phase
Max. 220 mW
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...