Appendix
A.3 MODBUS
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
269
A.3.16
Commands with the function code 0x06
Addressing the commands
Table A- 26 Commands
Offset Number of
registers
Name
Format
Applicable
MODBUS
function codes
Value range
Access
60002 1
Reset maximum values
Unsigned short 0x06
0
W
60003 1
Reset minimum values
Unsigned short 0x06
0
W
0 =
All
1 =
Active energy
import tariff 1
2 =
Active energy
import tariff 2
3 =
Active energy
export tariff 1
4 =
Active energy
export tariff 2
5 =
Reactive energy
import tariff 1
6 =
Reactive energy
import tariff 2
7 =
Reactive energy
export tariff 1
8 =
Reactive energy
export tariff 2
9 =
Apparent energy
tariff 1
10 = Apparent energy
tariff 2
11 = Process active
energy
12 = Process reactive
energy
60004 1
Reset energy counters
Unsigned short 0x06
13 = Process apparent
energy
W
60005 1
Synchronization of
demand period
Unsigned short 0x06
1 ... 60 min
W
0 =
On-peak tariff
60006 1
Switching tariff
Unsigned short 0x06
1 =
Off-peak tariff
W
60007 1
Acknowledge
diagnostics bits
Unsigned short 0x06
0-ffffh
W
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...