Appendix
A.3 MODBUS
SENTRON PAC4200
260
System Manual, 09/2009, A5E02316180B-02
Offset Number of
registers
Name
Format
Unit
Value range
Access
Byte 2 Port
Byte 2 0 ... 11
Byte 3 Bit
50253 2
Universal Counter 2 DI count
signal
Unsigned long -
Byte 3 0 ... 7
RW
61167 7
Digital Input Parameters
Unsigned long -
uchar
RW
61175 7
Digital Output Parameters
stOutputPara
-
uchar
RW
62101 8
Event Recording Parameters
stEventPara
-
uchar
RW
62301 27
Logically Combined Limit
Parameters
stCombLimitPa
ra
-
-
RW
1)
Subperiods 0 and 1: Fixed block method; subperiods 0 to 5: Rolling block method
2)
More information is given in the chapter under the also-see link.
See also
Value range for limit source (Page 260)
A.3.13
Value range for limit source
Assignment of the value range for the Limit x Source parameter
Table A- 23 Assignment of the values 0 to 241
Value
Assignment
0 =
Voltage a-n
1 =
Voltage b-n
2 =
Voltage c-n
3 =
Voltage a-b
4 =
Voltage b-c
5 =
Voltage c-a
6 =
Current a
7 =
Current b
8 =
Current c
9 =
Apparent Power a
10 =
Apparent Power b
11 =
Apparent Power c
12 =
Active Power a
13 =
Active Power b
14 =
Active Power c
15 =
Reactive Power a (VARn)
16 =
Reactive Power b (VARn)
17 =
Reactive Power c (VARn)
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...