Appendix
A.3 MODBUS
SENTRON PAC4200
270
System Manual, 09/2009, A5E02316180B-02
Offset Number of
registers
Name
Format
Applicable
MODBUS
function codes
Value range
Access
Byte 0 Bit 4
and Bit 7
Ports 0 ... 11
Byte 0
Bits 0 ... 3
Port bit
numbers
0 ... 7
Byte 1 = 0
Output port.
Port bit
number OFF
60008 1
Switching outputs (if
parameterized)
Unsigned short 0x06
Byte 1 = 1
Output port.
Port bit
number ON
W
Hi 0 ... 99, Lo 0 ... 1
HiByte Group
assignment
60009 1
Switching command for
vector group
Unsigned short 0x06
LoByte 0 = ON
1 = OFF
W
60010 1
Resetting the day energy
counter
Unsigned short 0x06
815
W
60011 1
Reset load profile
recording
Unsigned short 0x06
815
W
60012 1
Reset event recording
Unsigned short 0x06
815
W
60013 1
Set standard event
recording conditions
Unsigned short 0x06
815
W
60014 1
Set standard I/O
parameters
Unsigned short 0x06
815
W
65292 2
Increment date / time
Unsigned long
0x10
1-FFFFFFFFh
1)
W
1)
Time stamp low → adds the time stamp low to the current date and the current time
A.3.17
MODBUS standard device identification with the function code 0x2B
Addressing the MODBUS standard device identification
You can use MODBUS function code 0x2B on these device identification parameters.
Table A- 27 MODBUS standard device identification parameters
Object ID
Name
Format
Access
OID 0
Manufacturer
String
R
OID 1
Manufacturer device name
String
R
OID 2
Firmware version / bootloader version
String
R
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...