Storage capacity of the load profile memory
The data volume that occurs when a load profile is recorded depends on the length of the
period.
SENTRON PAC4200 can record load profile data for the following configuration over a
period of 40 days:
●
Fixed block:
Length of the demand period: 15 minutes
●
Rolling block:
Length of the subperiods: 15 minutes
This corresponds to a maximum of 3840 recorded periods.
This calculation applies to the ideal case in which the actual period length is identical to the
configured length for all periods over the complete load profile recording time. Any deviations
between the actual and configured period lengths additionally increase the data volume.
3.4.3
Current load profile data at the communication interfaces
Current load profile data
SENTRON PAC4200 supplies the load profile data for the current and instantaneous periods
at the communication interfaces.
●
The current period is the last completed period.
●
The instantaneous period is the period still in progress and has not yet been completed.
You can find more information on accessing the data via MODBUS in the Appendix.
See also
Measured variables for the load profile with the function codes 0x03 and 0x04 (Page 235)
3.4.4
Synchronization of the load profile
Synchronization time
The device expects the synchronization pulse at the start of the period.
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...