Appendix
A.3 MODBUS
SENTRON PAC4200
240
System Manual, 09/2009, A5E02316180B-02
Offset Number of
registers
Name
Format
Unit
Value range
Access
3151
6
Maximum Power Factor b with Time Float + time stamp -
0 … 1
R
3157
6
Maximum Power Factor c with Time
Float + time stamp -
0 … 1
R
3163
6
Maximum THD Voltage a-b referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3169
6
Maximum THD Voltage b-c referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3175
6
Maximum THD Voltage c-a referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3199
6
Maximum cos φ a with Time
Float + time stamp cos φ
a
-
R
3205
6
Maximum cos φ b with Time
Float + time stamp cos φ
b
-
R
3211
6
Maximum cos φ c with Time
Float + time stamp cos φ
c
-
R
3217
6
Maximum Displacement Angle a with
Time
Float + time stamp φ
-
R
3223
6
Maximum Displacement Angle b with
Time
Float + time stamp φ
-
R
3229
6
Maximum Displacement Angle c with
Time
Float + time stamp φ
-
R
3253
6
Maximum THD Voltage a with Time
Float + time stamp %
0 ... 100
R
3259
6
Maximum THD Voltage b with Time
Float + time stamp %
0 ... 100
R
3265
6
Maximum THD Voltage c with Time
Float + time stamp %
0 ... 100
R
3271
6
Maximum THD Current a with Time
Float + time stamp %
0 ... 100
R
3277
6
Maximum THD Current b with Time
Float + time stamp %
0 ... 100
R
3283
6
Maximum THD Current c with Time
Float + time stamp %
0 ... 100
R
3289
6
Maximum Distortion a with Time
Float + time stamp A
-
R
3295
6
Maximum Distortion b with Time
Float + time stamp A
-
R
3301
6
Maximum Distortion c with Time
Float + time stamp A
-
R
3307
6
Maximum Line Frequency with Time Float + time stamp -
45 ... 65
R
3313
6
Maximum 3-Phase Average Voltage
ph-n with Time
Float + time stamp V
-
R
3319
6
Maximum 3-Phase Average Voltage
ph-ph with Time
Float + time stamp V
-
R
3325
6
Maximum 3-Phase Average Current
with Time
Float + time stamp A
-
R
3331
6
Maximum Total Apparent Power with
Time
Float + time stamp VA
-
R
3337
6
Maximum Total Active Power with
Time
Float + time stamp W
-
R
3343
6
Maximum Total Reactive Power
(VARn) with Time
Float + time stamp VAR
-
R
3349
6
Maximum Total Power Factor with
Time
Float + time stamp -
-
R
3355
6
Maximum Neutral Current with Time Float + time stamp A
-
R
3361
6
Maximum Total Reactive Power
(VARtot) with Time
Float + time stamp VAR
-
R
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...