Startup
7.3 Parameterizing the device
SENTRON PAC4200
108
System Manual, 09/2009, A5E02316180B-02
7.3.4.3
Setting the conversion ratio of the voltage transducer
The factory setting is measurement direct on the system. At initial startup, the following steps
must be carried out if you want to measure using voltage transducers.
The conversion ratio can only be set if measurement using voltage transducers is set in the
device settings. Only then are the fields for primary and secondary voltage visible on the
display.
Figure 7-6
Device setting "USE PTs?"
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the current settings.
If the "PT PRIMARY" and "PT SECONDARY" fields are not visible, direct measurement
on the system is set. Switch from direct measurement to measurement using voltage
transducers. You can find the instructions for this in the "Measurement using voltage
transducers" chapter.
3.
Go to the "PT PRIMARY" device setting:
<F2>
or <F3>
4.
Open edit mode of the "PT PRIMARY" device setting:
<F4>
5.
Set the desired value:
<F2>
or <F3>
6.
Accept the value:
<F4>
The value of the primary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
7.
Go to the "PT SECONDARY" device setting:
<F2>
or <F3>
Proceed in exactly the same way as when entering the primary voltage.
The value of the secondary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
8.
Return to one of the selection menus or to the measured values display:
<F1>
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...