Technical data
11.1 Technical data
SENTRON PAC4200
178
System Manual, 09/2009, A5E02316180B-02
Digital inputs
Number
2 inputs
Input voltage
Rated value
24 V DC
Maximum input voltage
30 V DC (SELV or PELV supply)
Permissible signal level for
signal "0" detection
< 10 V DC
Permissible signal level for
signal "1" detection
> 19 V DC
Input current
For signal "1"
typ. 4 mA (24 V)
Max. input delay
Signal "0" to "1"
5 ms
Signal "1" to "0"
5 ms
Digital outputs
Number
2 outputs
Design/function
Switching output or pulse output
Operating voltage
12 to 24 V DC, max. 30 V DC (SELV or PELV
supply)
Output current
With "1" signal
Depends on the load and the external power supply
Continuous load
Max. 100 mA
(thermal overload protection)
Transient overload
max. 300 mA for a duration of 100 ms
Resistive load
100 mA
With "0" signal
max. 0.2 mA
Internal resistance
55 Ω
Short-circuit protection
Yes
Overvoltage category
CAT I
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30 to 500 ms
Minimal settable time frame
10 ms
Switching function
Max. output delay
With signal "0" to "1"
5 ms
With signal "1" to "0"
5 ms
Max. switching frequency
20 Hz
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...