Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
147
DIGITAL INPUT
Figure 9-9
"DIGITAL INPUT" device settings
DIG.INPUT
Digital input
ACTION
Method of using the digital input:
Range:
NONE:
The digital input is switched off.
PULSE INPUT:
Counting of input pulses.
Note:
A universal counter can be parameterized
for pulse counting. In the device settings
"ADVANCED > UNIVERSAL COUNTER",
set the field "SOURCE" to the value "DIG.
INPUT".
ON/OFF-PEAK:
Switching between tariffs. Off-peak if input
active.
TIME SYNC:
Synchronization of the internal clock ("Top
of minute").
The internal clock is put forward or back,
depending on whether the time is up to 30
seconds fast or slow.
If a pulse is not received for 20 minutes, an
event is recorded.
DEMAND SYNC:
Synchronization of power demand.
STATUS:
One event is recorded for each switching
operation.
START/STOP
Starts or stops the counters specified under
"Target". This depends on whether the
associated digital input is active or inactive.
If it is active, the action starts. If it is
inactive, the action stops.
COPY&RESET
Copies and resets the counters specified
under "Target". For this purpose, the
associated digital input is switched from
inactive to active.
RESET
Copies and resets the counters specified
under "Target". For this purpose, the
associated digital input is switched from
inactive to active.
Default value: NONE
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...