Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
145
LIM.VIOLATION
The digital output is switched on by a limit
violation and remains active while the limit
violation prevails.
The field "SOURCE" selects the limit to be
monitored. The definition of the limit is
stored in "ADVANCED > LIMITS".
ENERGY PULSE
The digital output outputs the
parameterized number of pulses or edges
per energy unit.
Default value: OFF.
MODE
The field is available when the action "ENERGY PULSE" is selected.
Pulses or edges are output.
PULSE: Pulses are output.
EDGE: Edges are output.
Default value: PULSE
W
(
('*(
38/6(
SYNC LENGTH
The field is available when the action "SYNC" is selected.
Length of the synchronization pulse. Time for which the signal at the
digital output is "high".
Range: 30 ... 500 ms
Default value: 100 ms