SEA SYSTEMS
INSTALLATION AND USE
STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 72 of 81
F.2) Signals table and STK3-B board terminals
LED Terminal
Function
HZ
Enable channel 1, controlled by impulse IS and ID
HC1
Control safety circuit status
HD3
POWER
Power LED, on and steady for correct power, blinking: power out of range
HD1
COMM
Cab serial communications LED: off: OK, on: connection error
HD2
ALARM
Plant alarm LED, blinking
H0C
Occupied LED (can be grouped with the OC output)
HC2
X11.1
Presence/sequence phase control
HC3
X10.4
Emergency device active
HC4
X9.5
KY connection/stick control
HC5 X9.6 K
∆
connection/stick control
HC6 X9.7
X10.3
KM connection/stick control
Enable emergency output
HU1
X5.7
Command K8, Door 1 Closure
HU2
X5.6
Command K7, Door 1 Opening
HU3
X5.3
Command K3, Door 2 Closure
HU4
X5.2
Command K2, Door 2 Opening
HAC
X6
Command K6, VMP valve
HU5 X7
Command K10, depends on start-up type: Command KY/K
∆
, Enable Soft Starter,
Command KE
HU6
X8
Command K11, YPT
HU7
X9.1-2
Command K1, enable remote alarm system output
HAS
X4.2
Command K5, Ascent
HAD
X4.5
Command K4, Descent, VMD
HAV
X3
Command K9, High Speed, VML
(8-7)
Safety Circuit enable
(8-6)
H1 X1_1
X1_1
XV1_1
Control 1, start safety chain
H2 X2_2
XV1_2
Control 2, Pit stop
H2E X2_2E
XV1_2E
Control 2E, Overrun
H5 X2_5
XC1_5
Control 5, Maintenance
H7 X2_7
XV1_7
C
ONTROL
7,
P
RELIMINARY DOOR
/
FLOOR CONTACTS
H8 XC1_8
XV1_8
C
ONTROL
8,
D
OOR FLOOR APPROACHING
H10
XV1_10
Control 10, Cab Door/block floor door
HIZ
XC1_IZ
Control floor zone safety circuit status
HIS XC2_IS1
XC2_IS2
IS Impulse, channel A encoder
HID XC2_ID1
XC2_ID2
ID Impulse, Channel B encoder
HRS XC2_RS
Ascent
phase
HRD XC2_RD
Descent
phase
HIM XC3_IM
Supplemental
impulse
HOC
XV2_OC Busy signal on floors Descent arrow on floors