STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 62 of 81
4.3 Service \ Taring
4.3.1 Service \ Taring \ Shaft Encoder
This function is only enabled if the shaft with encoder type has been selected in parameter 2.12. Otherwise
the following message will be displayed:
Not required!
This operation must
.1 Shaft Self-
tuning
ENT = Start
Execute the shaft self-tuning operation.
Press
ENT
to start the operation.
STS RD RS IM E
The operations will be automatically performed in descent and ascent
STS
Indicates the status of the maneuver execution:
0
= Test lowest floor
1
= Run up to highest floor
2
= Run down to lowest floor
ERR0 alarms in plant (See menus 1.3 and 1.5)
ERR1 invalid shaft signal status for RS, RD, and IM
(RD=0, RS=0, IM=0 at lowest floor).
ERR2 = encoder count between two minor 50 mm strips
ERR3 = No. programmed stops different from No. magnetic
strips counted (also considering the programmed reduced floors)
ERR4 = Magnetic strips, count when rising differs from count when
descending
ERR5 = Encoder count during rise different than decent run, difference
greater than 20 mm.
•
RD
Indicates the Status of the decent timing device SRD:
0 = open
1 = closed
•
RS
Indicates the Status of the rise timing device SRS:
0 = open
1 = closed
•
IM
Indicates the Status of the SIM impulse generator
0 = open
1 = closed
•
E
a variable number that indicates that the encoder is functioning.
The operation can be interrupted at any time using the
ESC
key
.1 Shaft Self-
tuning
Complete
Operation finished correctly.
Press ESC to exit.