STK3-GMV10 Control panel and Pre-wiring
For Hydraulic Elevators
MSTK3-GB
Rev.04
05/02/12
© Sea Systems S.r.l.
Page 53 of 81
3.3 Set-Up\Shaft Info (Shaft with Encoder)
Installation of Shaft sensors
Follow the Diagram 2.8.4.2 to install the shaft sensor system with encoder
3.3.1 Set-up\Info. Shaft\Distance Type
Floors 01 <> 02
Normal
… …
Ã
Ä
… …
Floors 11 <> 12
Normal
Inter-floor:
•
Normal. When the inter-floor distance is > 30 cm
•
Close. When the inter-floor distance is < 30 cm
3.3.2 Set-up\Info. Shaft\Floor threshold
2 Floor Threshold
Floor 01:xxxxx mm
… …
Ã
Ä
… …
2 Floor Threshold
Floor 12:xxxxx mm
Floor Threshold
It is automatically calculated during the automatic reading of the shaft.
Set-up to be performed after automatic reading of shaft.
3.3.3 Set-up\Info. Shaft\Ascent Stop
3 Ascent Stop
Floor 01: xx mm
… …
Ã
Ä
… …
3 Ascent Stop
Floor 12: xx mm
Ascent stop (range 0…63)
Set the quota referring to the floor threshold corresponding to the
ascent stop command.
It is automatically calculated during the automatic reading of the shaft.
Set-up to be performed after automatic reading of shaft.
3.3.4 Set-up\Info. Shaft\Descent Stop
4 Descent Stop
Floor 01: xx mm
… …
Ã
Ä
… …
4 Descent Stop
Floor 12: xx mm
Descent stop (range 0…9)
Set the quota referring to the floor threshold corresponding to the
ascent stop command.
It is automatically calculated during the automatic reading of the shaft.
Set-up to be performed after automatic reading of shaft.