9-12
Event Reports and Sequential Events Reporting
Date Code 20010521
SEL-387E Instruction Manual
Column Heading
Symbol
Definition
59G 1
2
b
Level 1 instantaneous residual overvoltage element
picked up
Level 2 instantaneous residual overvoltage element
picked up
Both Level 1 and Level 2 residual overvoltage elements
picked up
59Q
Q
Negative-sequence instantaneous overvoltage element
59Q picked up
81D 12
1
2
b
Frequency element 81D1 asserted
Frequency element 81D2 asserted
Both frequency elements asserted
81D 34
3
4
b
Frequency element 81D3 asserted
Frequency element 81D4 asserted
Both frequency elements asserted
81D 56
5
6
b
Frequency element 81D5 asserted
Frequency element 81D6 asserted
Both frequency elements asserted
TRP 12
1
2
b
TRIP1 asserted
TRIP2 asserted
TRIP1 and TRIP2 asserted
TRP 34
3
4
b
TRIP3 asserted
TRIP4 asserted
TRIP3 and TRIP4 asserted
DC 12
1
2
b
DC1 asserted
DC2 asserted
DC1 and DC2 asserted
DC34 3
4
b
DC3 asserted
DC4 asserted
DC3 and DC4 asserted
DEM
P12
1
2
b
PDEM1 asserted
PDEM2 asserted
PDEM1 and PDEM2 asserted
DEM
P3
3 PDEM3
asserted
DEM
N12
1
2
b
NDEM1 asserted
NDEM2 asserted
NDEM1 and NDEM2 asserted
DEM
N3
3 NDEM3
asserted
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......