Date Code 20020129
SEL-300 Series Relays Firmware Upgrade Instructions
B-3
SEL-387E Instruction Manual
6WHS
Disconnect any other serial port connection.
6WHS
Open HyperTerminal (on a personal computer running Windows, you would typically
click the
Start
button, point to Programs, and point to Accessories).
6WHS
Enter a name, select any icon, and click
OK
6WHS
Determine the computer serial port you will use to communicate with the relay
(Figure B.2) and click
OK
.
6WHS
Establish serial port communications parameters.
Note that these settings for your computer (Figure B.3) must match the settings you
recorded earlier for the relay (hardware and software flow control settings, for
example, should match what you recorded earlier for the relay RTSCTS setting). If
computer settings do not match relay settings, change the computer settings to match
relay settings.
Figure B.1: Establishing a Connection
Figure B.2: Determining the
Computer Serial Port