Date Code 20010521
Event Reports and Sequential Events Reporting
9-3
SEL-387E Instruction Manual
PULSE and TRIGGER Commands
The
PUL
serial port/front-panel command is used to assert the output contacts for testing
purposes or for remote control. If an output contact is asserted with the
PUL
command, a
standard 15-, 29-, or 60-cycle event report is also generated. Because the
PUL
command
generates an event report, precautions should be taken to retrieve and store any existing event
reports of interest that presently may be in the relay, before testing the output contacts with the
PUL
command. Failure to do so may result in some or all of the existing reports being
overwritten, when
PUL
commands are issued.
The sole function of the
TRI
serial port command is to generate standard 15-, 29-, or 60-cycle
event reports, primarily for testing purposes. Simply type
TRI<ENTER>
, to execute the
command.
See
Section 7: Serial Port Communications and Commands
for more information on the serial
port commands
TRI
and
PUL
.
Standard Event Report Summary
Each time the relay generates a standard 15-, 29-, or 60-cycle event report, it also generates a
corresponding event summary (see Figure 9.1). Event summaries contain the following
information:
Relay and terminal identifiers (settings RID and TID)
Date and time when the event was triggered
Event type
Front-panel targets at the time of trip
Phase (IA, IB, IC) currents for the three (3) current winding inputs
Phase (VA, VB, VC) voltage inputs
Percent volts/hertz
This event summary information is also contained in the corresponding standard 15-, 29-, or 60-
cycle event report. The identifiers, date, and time information is at the top of the standard 15-,
29-, or 60-cycle event report, and the other information follows at the end. See Figure 9.2.
The example event summary in Figure 9.1 corresponds to the full-length standard 15-cycle event
report in Figure 9.2.
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
Event: TRIG
Targets:
Winding 1 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding 2 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding 3 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding X Voltages (V Sec), ABC: 123.1 123.1 123.1
Volts/Hertz Percent: 123.1
=>>
Figure 9.1: Example Event Summary
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......