4
SEL-387E Relay Command Summary
Date Code 20020129
SEL-387E Instruction Manual
EVE DIF3 n
Show differential element 3 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE R n
Show raw analog data event report number n, with 1/16-cycle resolution.
Attach Sm for 1/m cycle resolution. (m = 4, 8, 32, 64)
GRO
Display active setting group number.
GRO n
Switch to Setting Group n. (Will not function if any SSn Relay Word bit is asserted.)
HIS n
Show brief summary of the n latest event reports.
HIS C
Clear the brief summary and corresponding standard event reports.
INI
Reports the number and type of interface boards in the relay.
IRI
Force synchronization attempt of internal relay clock to IRIG-B time-code input.
MET k
Display metering data, in primary amperes. Enter number k to scroll metering k times
on screen.
MET D k
Display demand metering data, in primary amperes. Enter number k to scroll metering
k times on screen.
MET DIF k
Display differential metering data, in multiples of tap. Enter number k to scroll
metering k times on screen.
MET E
Display energy metering data.
MET H
Generate harmonic spectrum report for all input currents, showing first to 15th
harmonic levels in secondary amperes.
MET P k
Display peak demand metering data, in primary amperes. Enter number k to scroll
metering k times on screen.
MET RD n
Reset demand metering values. (n = 1, 2, 3, A)
MET RP n
Reset peak demand metering values. (n = 1, 2, 3, A)
MET SEC k
Display metering data (magnitude and phase angle), in secondary amperes. Enter
number k to scroll metering k times on screen.
OPE n
Assert the OCn Relay Word bit. Used to open breaker n if OCn is assigned to an
output contact. JMP6B has to be in place to enable this command.
PUL y k
Pulse output contact y (y = OUT101,…,OUT107, OUT2XX, OUT3XX, and ALARM).
Enter number k to pulse for k seconds [k = 1 to 30 (seconds)], otherwise pulse time
is 1 second. JMP6B has to be in place to enable this command.
QUI
Quit. Returns to Access Level 0. Returns front-panel LEDs to the default targets.
SER n
Show the latest n rows in the Sequential Events Recorder (SER) event report.
SER m n
Show rows m through n in the Sequential Events Recorder (SER) event report.
SER d1
Show rows in the Sequential Events Recorder (SER) event report for date d1.
SER d1 d2
Show rows in the Sequential Events Recorder (SER) event report from date d1 to d2.
Entry of dates is dependent on the Date Format setting DATE_F (= MDY or YMD).
SER C
Clear the Sequential Events Recorder (SER) event reports from memory.
SHO n
Show relay group n settings. Shows active group if n is not specified.
SHO G
Show relay global settings.
SHO P
Show port settings and identification of port to which user is connected.
SHO P n
Show port settings for Port n (n =1, 2, 3, 4).
SHO R
Show Sequential Events Recorder (SER) settings.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......