Date Code 20020129
Testing and Troubleshooting
10-39
SEL-387E Instruction Manual
Step 11.
Purpose: Verify the Level 2 Volts/Hertz delay setting, when
24CCS = DD
and
24D2D1 < 24D2D2
.
Method: Execute
the
SHOWSET
command via the relay front panel or serial port
and verify the setting (i.e.,
SHO 24CCS<ENTER, SHO
24D2D1<ENTER>
).
24CCS
should be set to
DD; 24D2D1
should be
less than
24D2D2.
Step 12.
Purpose: Display the appropriate Relay Word bit on the front-panel LEDs.
Method: Execute
the
TARGET
command (i.e.,
TAR F 24C2T<ENTER>
). The
SEL-387E Relay now displays the state of the volts/hertz elements on the
bottom row of front-panel LEDs.
Step 13.
Purpose: Apply balanced three-phase voltage and change the voltage until the
appropriate LED illuminates.
Method: Apply balanced three-phase voltages as shown in Figure 10.5. Change the
voltage to a value above the
24D2P1
setting. The
24C2T
LED should
illuminate
24D2D1
seconds later, within ±0.1% of setting ±4.2 ms (at 60
Hz).
Step 14.
Purpose: Verify the Level 2 volts/hertz delay setting,
when
24CCS = DD
and
24D2D2 < 24D2D1
.
Method: Execute
the
SHOWSET
command via the relay front panel or serial port
and verify the setting (i.e.,
SHO 24CCS<ENTER, SHO
24D2D2<ENTER>
).
24CCS
should be set to
DD; 24D2D2
should be
less than
24D2D1.
Step 15.
Purpose: Display the appropriate Relay Word bit on the front-panel LEDs.
Method: Execute
the
TARGET
command (i.e.,
TAR F 24C2T<ENTER>
). The
SEL-387E Relay now displays the state of the volts/hertz elements on the
bottom row of front-panel LEDs.
Step 16.
Purpose: Apply balanced three-phase voltage and change the voltage until the
appropriate LED illuminates.
Method: Apply balanced three-phase voltages as shown in Figure 10.5. Change the
voltage to a value above the
24D2P2
setting. The
24C2T
LED should
illuminate
24D2D2
seconds later, within ±0.1% of setting ±4.2 ms (at 60
Hz).
Step 17.
Purpose: Verify the Level 2 volts/hertz delay settings, when
24CCS = ID
.
Method: Execute
the
SHOWSET
command via the relay front panel or serial port
and verify the setting (i.e.,
SHO 24CCS<ENTER
).
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......