Date Code 20020129
Serial Port Communications and Commands
7-25
SEL-387E Instruction Manual
QUI (Quit)
Access Levels 0, 1, B, 2
The
QUI
command returns the relay to Access Level 0 from Level 1, B, or 2. The command
displays the relay settings RID, TID, date, and time of
QUI
command execution.
Use the
QUI
command when you finish communicating with the relay, to prevent unauthorized
access. The relay automatically returns to Access Level 0 after a certain inactivity time
dependent on the SET P setting T_OUT.
==>QUI<ENTER>
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
=
RES (RESET51 -- Reset Inverse-Time O/C Elements)
Access Level 2
The
RES
command clears the inverse-time overcurrent element accumulators (phase, negative-
sequence, and residual) for all three windings. It also clears the combined overcurrent phase and
residual inverse-time elements. This command is useful in testing the inverse-time elements,
because it mimics the action of immediately returning an electromechanical disk to the starting
position. This command can save time in waiting for some units to reset according to their
electromechanical reset equations in
Section 3: Differential, Restricted Earth Fault,
Overcurrent, Voltage, and Frequency Elements
.
The relay will ask “Reset 51 Elements (Y/N) ?” when given the
RES
command. If No, it will
abort the command. If Yes, it will respond “All Time-Overcurrent Element Accumulators
Cleared.” This command is not likely to have much use in normal in-service relay operation.
SER (Sequential Events Recorder)
Access Levels 1, B, 2
The
SER
command displays the last 512 sequential events records. To limit the number of
records displayed, use number or date parameters with the
SER
command.
SER d1
shows only
events triggered on the date specified by d1.
SER d1 d2
shows only events triggered on or
between the specified dates.
SER m
shows the most recent m events.
SER m n
shows event
records m through n. The following is an example of the SER report. See
Section 9: Event
Reports and Sequential Events Reporting
for a complete description of the report.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......