Date Code 20010521
Event Reports and Sequential Events Reporting
9-23
SEL-387E Instruction Manual
A calculation of the phasor using the previous pair, X = -1375 and Y = -2376, yields a
calculation of:
IA = 2745 A
µ
-120.0
Thus, the phasor rotates in a counter-clockwise direction in 90-degree increments, as expected,
when successive pairs of samples are used for making the calculation.
S
EQUENTIAL
E
VENTS
R
ECORDER
(SER) E
VENT
R
EPORT
Figure 9.8 demonstrates an example SER event report.
=>>SER 2/26/97 2/27/97<ENTER>
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
FID=SEL-387E-R-V-D
# DATE TIME ELEMENT STATE
4 2/26/97 10:33:54.873 TRIP3 Asserted
3 2/26/97 10:33:55.373 TRIP3 Deasserted
2 2/27/97 10:34:06.872 CLS3 Asserted
1 2/27/97 10:34:07.372 CLS3 Deasserted
=>>
Figure 9.8: Example SER Event Report
SER Event Report Row Triggering and ALIAS Settings
The relay triggers (generates) a row in the SER event report for any change of state in any one of
the elements listed in the SER1, SER2, SER3, or SER4 trigger settings. Use port command
SHO R
to view the settings, or
SET R
to set them. The factory default settings are:
SER1 = IN101,IN102,IN103,IN104,IN105,IN106
SER2 = OUT101,OUT102,OUT103,OUT104,OUT105,OUT106,OUT107
SER3 = 0
SER4 = 0
The elements are Relay Word bits from Tables 5.7 to 5.9. Each element is looked at individually
to see if it asserts or deasserts. Any assertion or deassertion of a listed element triggers a row in
the SER event report. For example, setting SER1 contains all six of the optoisolated inputs. Any
time dc voltage is applied to, or removed from, one of these inputs, a row is triggered in the SER
event report.
In the SER settings are 20 settings by which the user can redefine the names of Relay Word bits
in the SER report, to make the entries more readily identifiable to the user. The settings are
ALIAS1 to ALIAS20. If they are not set, they are listed as, for example, ALIAS1=NA.
To rename a Relay Word bit with an ALIASn setting, use SET R to access the settings. For each
“ALIASn =” setting, list the bit name, then a space, then the desired name, which can contain
any combination of 15 letters, numbers, and underscores. For example, one setting might be
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......