Date Code 20020129
SEL-387E Relay Command Summary
3
SEL-387E Instruction Manual
TAR R
Return front-panel LED targets to regular operation and reset the tripping front-panel
targets.
TAR n k
Show Relay Word row n status (n = 0 through 41). Enter number k to scroll Relay
Word row n status k times on screen.
Append F to display targets on the front panel, second row of LEDs.
TIM
Show or set time (24-hour time). Show time presently in the relay by entering just
TIM. Example time 22:47:36 is entered with command TIM 22:47:36.
TRI
Trigger an event report.
A
CCESS
L
EVEL
B C
OMMANDS
$FFHVV
/HYHO%
&RPPDQGV
The Access Level B commands allow the user to control breakers and output contacts.
All Access Level 1 commands can also be executed from Access Level B. The screen
prompt is: ==>
ACC
Enter Access Level 1. If the main board password jumper (JMP6A) is not in place, the
relay prompts for the entry of the Access Level 1 password in order to enter Access
Level 1.
2AC
Enter Access Level 2. If the main board password jumper (JMP6A) is not in place, the
relay prompts for the entry of the Access Level 2 password in order to enter Access
Level 2.
BRE
Breaker report shows trip counters, trip currents, and wear data for up to four breakers.
BRE R n
Reset trip counters, trip currents, and wear data for Breaker n (n = 1, 2, 3, A).
BRE W n
Pre-set the percent contact wear for each pole of Breaker n (n = 1, 2, 3).
CEV n
Show compressed winding event report number n, at 1/4-cycle resolution.
Attach DIF for compressed differential element report, at 1/4-cycle resolution.
Attach R for compressed raw winding data report, at 1/16-cycle resolution.
Attach Sm for 1/m cycle resolution. (m = 4 or 8 for filtered data; m = 4, 8, 16, 32, or
64 for raw data)
CLO n
Assert the CCn Relay Word bit. Used to close Breaker n if CCn is assigned to an
output contact. JMP6B has to be in place to enable this command.
DAT
Show date presently in the relay.
DAT m/d/y
Enter date in this manner if Date Format setting DATE_F = MDY.
DAT y/m/d
Enter date in this manner if Date Format setting DATE_F = YMD.
EVE n
Show standard event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE D n
Show digital data event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE DIF1 n
Show differential element 1 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE DIF2 n
Show differential element 2 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......