![Schweitzer Engineering Laboratories SEL-387E Скачать руководство пользователя страница 220](http://html1.mh-extra.com/html/schweitzer-engineering-laboratories/sel-387e/sel-387e_instruction-manual_1216724220.webp)
SEL-387E Settings Sheets
Page 6 of 27
Group Settings (SET Command)
Date
Group
Date Code 20020129
Phase Inst. O/C Level 3 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50P23P
=
Phase Inst. O/C Level 4 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50P24P
=
Phase Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
(OFF,
0.1–3.2 A secondary) (1 A)
51P2P
=
Phase Inv.-Time O/C Curve (U1–U5, C1–C5) 51P2C
=
Phase Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51P2TD
=
Phase Inv.-Time O/C EM Reset (Y, N)
51P2RS
=
51P2 Torque Control (SEL
OGIC
control equation)
51P2TC =
W
INDING
2 N
EGATIVE
-S
EQUENCE
O/C E
LEMENTS
Note: All negative-sequence element pickup settings are in terms of 3I
2
.
Neg.-Seq. Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50Q21P
=
Neg.-Seq. Level 1 O/C Delay (0.5–16000 cycles)
50Q21D
=
50Q21 Torque Control (SEL
OGIC
control equation)
50Q21TC =
Neg.-Seq. Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50Q22P
=
50Q22 Torque Control (SEL
OGIC
control equation)
50Q22TC =
Neg.-Seq. Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
(OFF,
0.1–3.2 A secondary) (1 A)
51Q2P
=
Neg.-Seq. Inv.-Time O/C Curve (U1–U5, C1–C5) 51Q2C
=
Neg.-Seq. Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51Q2TD
=
Neg.-Seq. Inv.-Time O/C EM Reset (Y, N)
51Q2RS
=
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......