Date Code 20020129
Serial Port Communications and Commands
7-31
SEL-387E Instruction Manual
Settings cannot be entered or modified with this command. Change settings with the
SET G
command from Access Level 2. Refer to individual elements in
Section 3: Differential,
Restricted Earth Fault, Overcurrent, Voltage, and Frequency Elements
and to
Section 6:
Setting the Relay
for information on settings.
SHO P (Show Port Settings)
Access Levels 1, B, 2
SHO P displays the relay serial port settings. The port settings include the communications and
protocol settings. The syntax of the
SHO P
command follows:
SHO P n
Setting
<ENTER>
The two parameters are optional and perform the following functions:
n
specifies the serial port number (1, 2, 3, or 4). Default is the port issuing the command.
Setting
specifies the setting name with which to begin. The default is the first setting.
Entering
SHO P<ENTER>
is an easy way to identify the port to which you are presently
connected.
Settings cannot be entered or modified with this command. Change settings with the
SET P
command from Access Level 2. The following example shows the factory default settings.
Refer to
Section 6: Setting the Relay
for Settings Sheets.
SHO R (Show SER Settings)
Access Levels 1, B, 2
SHO R
displays the Sequential Events Recorder settings. The syntax of the
SHO R
command
follows:
SHO R
Setting
<ENTER>
Setting
specifies the setting name with which to begin. The default is the first setting.
Settings cannot be entered or modified with this command. Change settings with the
SET R
command from Access Level 2. Refer to individual elements in
Section 3: Differential,
Restricted Earth Fault, Overcurrent, Voltage, and Frequency Elements
and to
Section 6:
Setting the Relay
for information on settings.
STA (Status Report)
Access Levels 1, B, 2
The
STA
command displays a report of the self-test diagnostics. The relay automatically
executes the
STA
command whenever the self-test software enters a warning or failure state.
You may repeat the
STA
command by appending a number as a repeat count parameter. Type
STA 4<ENTER>
to view the status information four times.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......