8-16
Front-Panel Interface
Date Code 20020129
SEL-387E Instruction Manual
The relay will pulse the output contact for one second, then return to the contact selection screen,
in case there are more contacts to test.
<CANCEL>
will return to the main CNTRL menu.
<EXIT>
will abort the command and return to the default display.
Note:
The CNTRL function, while useful during testing, should not be used while the relay is
actually in service. During the one-second interval while contact OUT10X is being
pulsed, all other OUT10Y contacts are frozen in their existing state and are not permitted
to change. This could prevent a trip or other vital output from being issued during the
pulse interval.
If
Close
is selected, the next screen prompts for the breaker (Bk1 to Bk4) to be closed. Use the
right/left arrow keys and
<SELECT>
to choose, for example Bk1. The relay then asks
“Close
Bkr 1? Yes No
.
”
Use the right/left arrow keys and
<SELECT>
to choose. If Yes, the relay
asserts the CC1 Relay Word bit. If CC1 has been assigned to the CL1 Close Logic setting, the
breaker will close. If No is selected, the relay returns to the Close menu.
If
Open
is selected, a sequence exactly like the one for Close takes place. If Yes is selected, the
relay asserts Relay Word bit OC1 for Bkr 1, and if this bit has been assigned to the TR1 Trip
Logic setting, the breaker will open. The
TRIP
front-panel LED will also light. It can be turned
off by pushing the TARGET RESET button or by the
TAR R
serial port command.
Because all three CNTRL functions are legitimate event types, an Event Report will be triggered
whenever any is activated. An automatic message will be sent to any port set to receive
messages. If the output contacts are listed as SER triggers, the contact assertion and deassertion
will appear in the SER report, with time tags. Contact operate timing can thus be easily
analyzed.
GROUP
The GROUP function is identical to the
GRO
and
GRO n
(n = 1 to 6) serial port commands.
When you select the
<GROUP>
button, the relay display shows “Active Group 1” (for
example), and inquires whether you want to
Change
or
Exit
. Use the right/left arrow keys and
<SELECT>
to choose.
If Change is selected, the display shows
Change to Group
in the first line and the present group
number in the second line. Use the up/down arrows and
<SELECT>
to choose another group.
The relay will ask for a Yes/No verification of the change. Use the right/left arrow keys and
<SELECT>
to choose. The change will be made and the ALARM contact pulsed for one
second if Yes is chosen, and if SS1 through SS6 are not asserted or assigned. These group
selection settings always take precedence over the
GROUP
command function.
<CANCEL>
may be used to return to an earlier menu.
<EXIT>
will abort the command and
return to the default display.
Secondary Function Review
The secondary button functions come into effect as soon as one of the buttons for the above
primary functions has been pushed. These secondary functions remain in effect until a primary
function has been completed, aborted or exited, and the display has returned to the default
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......