Date
Group
Date Code 20020129
Operating Quantity from W 1, W 2 (1, 2, 12)
32IOP
=
1
Positive-Sequence Current Restraint Factor, I0/I1 (0.02–0.50) a0
=
0.10
Residual Current Sensitivity Threshold
(0.25–15.00 A secondary) (5 A)
50GP
=
0.10
(0.05–3.00 A secondary) (1 A)
0.10
W
INDING
1 O/C E
LEMENTS
W
INDING
1 P
HASE
O/C E
LEMENTS
Phase Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
50P11P
=
20.00
(OFF,
0.05–20.00 A secondary) (1 A)
4.00
Phase Level 1 O/C Delay (0–16000 cycles)
50P11D
=
5
50P11 Torque Control (SEL
OGIC
control equation)
50P11TC = 1
Phase Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
50P12P
=
OFF
(OFF,
0.05–20.00 A secondary) (1 A)
OFF
50P12 Torque Control (SEL
OGIC
control equation)
50P12TC = 1
Phase Inst. O/C Level 3 PU
(OFF,
0.25–100.00 A secondary) (5 A)
50P13P
=
0.50
(OFF,
0.05–20.00 A secondary) (1 A)
0.10
Phase Inst. O/C Level 4 PU
(OFF,
0.25–100.00 A secondary) (5 A)
50P14P
=
4.00
(OFF,
0.05–20.00 A secondary) (1 A)
0.80
Phase Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
51P1P
=
4.00
(OFF,
0.1–3.2 A secondary) (1 A)
0.80
Phase Inv.-Time O/C Curve (U1–U5, C1–C5) 51P1C
=
U2
Phase Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51P1TD
=
3.00
Phase Inv.-Time O/C EM Reset (Y, N)
51P1RS
=
Y
51P1 Torque Control (SEL
OGIC
control equation)
51P1TC =
1
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......