7-10
Serial Port Communications and Commands
Date Code 20020129
SEL-387E Instruction Manual
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
FID=SEL-387E-R-V-D
SELF TESTS
W=Warn F=Fail
IAW1 IBW1 ICW1 IAW2 IBW2 ICW2
OS 123 123 123 123 123 123
IAW3 IBW3 ICW3 VAWX VBWX VCWX
OS 123 123 123 123 123 123
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 1.12 1.12 -1.12 12.12 -12.12 12.12 -12.12
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
123.1 OK OK OK OK OK OK
Relay Enabled
=>>
RID and TID settings for the active group
Date and time the failure or warning was detected
Firmware identification string
Individual self-test results
Relay protection enabled or disabled indication
Event Summary Message
An automatic message is generated each time an event is triggered. The message is a summary
of the event.
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
Event: TRIG
Targets:
Winding 1 Currents (A Sec), ABC: 123.0 123.0 123.0
Winding 2 Currents (A Sec), ABC: 123.0 123.0 123.0
Winding 3 Currents (A Sec), ABC: 123.0 123.0 123.0
Winding X Voltages (V Sec), ABC: 123.0 123.0 123.0
Volts/Hertz Percent: 0.0
=>>
RID and TID settings for the active group
Date and time the event was triggered
The event type
Target information
All phase currents and voltages
Access Levels
Commands can be issued to the relay via the serial port to view metering values, change relay
settings, etc. The available ASCII serial port commands are listed in Figure 7.2 and summarized
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......