Date Code 20020129
Distributed Network Protocol (DNP) 3.00
G-19
SEL-387E Instruction Manual
==>DNP AI<ENTER>
Enter the new DNP Analog Input map
112;5 28;0.2 17:10 1;1:15<ENTER>
==>
These settings will cause the value at index 112 (now at index 0) to be multiplied by five before
it is reported. Similarly, the value at index 28 (now at index 1) will be multiplied by 0.2 before it
is reported. Both of these values will use the default dead-band. The value at index 17 (now at
index 2) is left for default scaling, but uses a dead-band of +/– 10 counts. Similarly, the value
that was at index 1 (now at index 3) is now scaled by 1 and uses a dead-band of +/– 15 counts.
Modem Support
The modem handling will only be applied when the port settings include the following:
PROTOCOL = DNP
MODEM = Y
On power-up and settings change, the relay shall initialize the modem by issuing the string
"+++AT" followed by the MSTR string and <CR>. This will initialize the modem. The MSTR
(modem string) is a port setting visible only when the protocol setting is DNP. The MSTR
setting is a series of ASCII characters that initialize the modem by sending the modem a series of
commands.
If someone calls in, the modem will send "RING" and "CONNECT" messages to the relay.
These messages, as well as all messages received while DCD is low, shall be ignored. All DNP
messages received while connected shall be treated normally.
If the relay needs to send an unsolicited message and it is not currently connected, it must
attempt to make a connection by sending the string "+++ATDT" followed by the phone number
and <CR>. It shall then wait for a "CONNECT" message. Once "CONNECT" is received and
CTS is asserted, the relay can consider itself connected and continue its transaction. If
connection is not achieved within MDTIME seconds of initiating the phone call, the relay shall
issue the command "+++ATH<CR>" and wait at least MDRETI seconds before trying again and
try MDRETN times before giving up. If it fails to connect in the first try, it will try again at a
later time every six hours.
If the relay initiates a connection, it shall disconnect once there have been no transactions for
TIMEOUT time, using the disconnect command "+++ATH<CR>". Also, if an outside caller
connects to the modem in the SEL-387E, the SEL-387E will disconnect the modem if there have
been no transactions for the TIMEOUT time.
Note 1
: Because of the connection requirements described here, it will not be possible to use
hardware flow control (RTSCTS) with the modem. This means that it is important to
select a port baud rate low enough that the modem connection will not end up slower,
or there will be a high likelihood of losing characters.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......