13.7
Date Code 20060320
Instruction Manual
SEL-311C Relay
Testing and Troubleshooting
Testing Methods and Tools
Testing Via Front-Panel Indicators
Display the state of relay elements, inputs, and outputs by using the front-
panel or serial port
TAR
commands. Use this method to verify the pickup
settings of protection elements.
Access the front-panel
TAR
command from the front-panel
{OTHER}
pushbutton menu.
Step 1. To display the state of the 51PT element on the front-panel
display, press the
{OTHER}
pushbutton.
Step 2. Move your cursor to the
TAR
option, and press
{SELECT}
.
Step 3. Press the up arrow pushbutton until
TAR 28
is displayed on the
top row of the LCD.
The bottom row of the LCD displays all elements asserted in
Relay Word Row 28. The relay maps the state of the elements
in Relay Word Row 28 on the bottom row of LEDs. The 51PT
element state is reflected on the LED labeled
B
. See
for the correspondence between the Relay Word
elements and the
TAR
command.
Step 4. To view the 51PT element status from the serial port, issue the
TAR 51PT
command.
The relay will display the state of all elements in the Relay
Word row containing the 51PT element.
Review
TAR
and
Section 11: Front-Panel Interface (Only
for further details on displaying element status via the
TAR
commands.
Testing Via Output Contacts
You can set the relay to operate an output contact for testing a single element.
Use the
SET L
command (SEL
OGIC
control equations) to set an output
contact (e.g.,
OUT101
–
OUT108
for Model 0311C00
x
) to the element under test.
The available elements are the Relay Word bits referenced in
and
.
Use this method especially for time testing time-overcurrent elements. For
example, to test the phase time-overcurrent element 51PT via output contact
OUT104
, make the following SEL
OGIC
setting:
OUT104 =
51PT
Time-overcurrent curve and time-dial information can be found in
. Do not forget to reenter the correct relay settings when you
are finished testing and are ready to place the relay in service.
Testing Via Sequential Events Recorder
You can set the relay to generate an entry in the Sequential Events Recorder
(SER) for testing relay elements. Use the
SET R
command to include the
element(s) under test in any of the SER trigger lists (SER1–SER3). See
Section 12: Standard Event Reports and SER
.
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...