1.12
SEL-311C Relay
Instruction Manual
Date Code 20060320
Introduction and Specifications
Specifications
Currents
(0.50–1.25 A; 45–65 Hz)
(5 A nominal)
(0.10–0.25 A; 45–65 Hz)
(1 A nominal)
Magnitudes:
± 4%
Angles:
± 1.5° @ 25°C
± 2.0° over the full temperature range
Currents
(1.25–7.50 A; 45–65 Hz)
(5 A nominal)
(0.25–2.50 A; 45–65 Hz)
(1 A nominal)
Magnitudes:
± 2%
Angles:
± 1.0° @ 25°C
± 1.5° over the full temperature range
Substation Battery Voltage Monitor Specifications
Pickup Range:
20–300 Vdc, 1 Vdc steps
Pickup Accuracy:
± 2% ± 2 V of setting
Timer Specifications
Reclosing Relay Pickup: 0.00–999,999.00 cycles,
0.25-cycle steps
Other Timers:
0.00–16,000.00 cycles, 0.25-cycle steps
Pickup/
Dropout Accuracy for
All Timers:
± 0.25 cycle and ±0.1% of setting
Mho Phase Distance Elements
Zones 1–4 Impedance Reach
Setting Range:
OFF, 0.05 to 64
Ω
sec, 0.01
Ω
steps
(5 A nominal)
OFF, 0.25 to 320
Ω
sec, 0.01
Ω
steps
(1 A nominal)
Minimum sensitivity is controlled by
the pickup of the supervising phase-
to-phase overcurrent elements for
each zone.
Accuracy:
± 5% of setting at line angle
for 30
≤
SIR
≤
60
± 3% of setting at line angle
for SIR < 30
Transient Overreach:
< 5% of setting plus steady-state
accuracy
Zones 1–4 Phase-to-Phase Current Fault Detectors (FD)
Setting Range:
0.5–170.00 A
P-P
secondary,
0.01 A steps (5 A nominal)
0.1–34.00 A
P-P
secondary,
0.01 A steps (1 A nominal)
Accuracy:
± 0.05 A and ±3% of setting
(5 A nominal)
± 0.01 A and ±3% of setting
(1 A nominal)
Transient Overreach:
< 5% of pickup
Maximum Operating
Time:
See pickup and reset time curves in
and
Mho and Quadrilateral Ground Distance Element
Zones 1–4 Impedance Reach
Mho Element Reach:
OFF, 0.05 to 64
Ω
sec, 0.01
Ω
steps
(5 A nominal)
OFF, 0.25 to 320
Ω
sec, 0.01
Ω
steps
(1 A nominal)
Quadrilateral Reactance
Reach:
OFF, 0.05 to 64
Ω
sec, 0.01
Ω
steps
(5 A nominal)
OFF, 0.25 to 320
Ω
sec, 0.01
Ω
steps
(1 A nominal)
Quadrilateral Resistance
Reach:
OFF, 0.05 to 50
Ω
sec, 0.01
Ω
steps
(5 A nominal)
OFF, 0.25 to 250
Ω
sec, 0.01
Ω
steps
(1 A nominal)
Minimum sensitivity is controlled by
the pickup of the supervising phase
and residual overcurrent elements for
each zone.
Accuracy:
± 5% of setting at line angle
for 30
≤
SIR
≤
60
± 3% of setting at line angle
for SIR < 30
Transient Overreach:
< 5% of setting plus steady-state
accuracy
Zones 1–4 Phase and Residual Current Fault Detectors (FD)
Setting Range:
0.5–100.00 A secondary, 0.01 A steps
(5 A nominal)
0.1–20.00 A secondary, 0.01 A steps
(1 A nominal)
Accuracy:
± 0.05 A and ±3% of setting
(5 A nominal)
± 0.01 A and ±3% of setting
(1 A nominal)
Transient Overreach:
< 5% of pickup
Max. Operating Time:
See pickup and reset time curves in
and
Instantaneous/Definite-Time Overcurrent Elements
Pickup Range:
OFF, 0.25–100.00 A, 0.01 A steps
(5 A nominal)
OFF, 0.05–20.00 A, 0.01 A steps
(1 A nominal)
Steady-State Pickup
Accuracy:
± 0.05 A and ±3% of setting
(5 A nominal)
± 0.01 A and ±3% of setting
(1 A nominal)
Transient Overreach:
< 5% of pickup
Time Delay:
0.00–16,000.00 cycles, 0.25-cycle steps
Timer Accuracy:
± 0.25 cycle and ±0.1% of setting
Maximum Operating
Time:
See pickup and reset time curves in
and
Time Overcurrent Elements
Pickup Range:
OFF, 0.25–16.00 A, 0.01 A steps
(5 A nominal)
OFF, 0.05–3.20 A, 0.01 A steps
(1 A nominal)
Steady-State Pickup
Accuracy:
± 0.05 A and ±3% of setting
(5 A nominal)
± 0.01 A and ±3% of setting
(1 A nominal)
Time Dial Range:
0.50–15.00, 0.01 steps (US)
0.05–1.00, 0.01 steps (IEC)
Curve Timing Accuracy: ± 1.50 cycles and ± 4% of curve time for
current between 2 and 30 multiples of
pickup
Under- and Overvoltage Elements
Pickup Range:
OFF, 0.00–150.00 V, 0.01 V steps
(various elements)
OFF, 0.00–260.00 V, 0.01 V steps
(phase-to-phase elements)
Steady-State Pickup
Accuracy:
± 1 V and ±5% of setting
Transient Overreach:
< 5% of pickup
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...