12.10
SEL-311C Relay
Instruction Manual
Date Code 20060320
Standard Event Reports and SER
Standard 15/30/60/180-Cycle Event Reports
Other figures help in understanding the information available in the event
report current or voltage columns:
➤
shows how event report current column data relate
to the actual sampled current waveform and rms current values.
➤
shows how event report current column data can be
converted to phasor rms current values.
Output, Input, Protection, and Control Columns
summarizes the event report output, input, protection, and control
columns. See
and
for more information on the Relay Word
.
Table 12.4
Output, Input, Protection, and Control Element Event Report Columns
(Sheet 1 of 6)
Column Heading
Corresponding
Elements (Relay
Word Bits)
Symbol
Definition
All columns
.
Element/input/output not picked up
or not asserted, unless otherwise stated.
ZAB
a
MAB1
MAB2
MAB3
MAB4
1
2
3
4
If Zone 1 AB phase-phase distance element (MAB1) set
If Zone 2 AB phase-phase distance element (MAB2) set, not ZAB1
If Zone 3 AB phase-phase distance
element (MAB3) set, not ZAB1 or ZAB2
If Zone 4 AB phase-phase distance
element (MAB4) set, not ZAB1 or ZAB2 or ZAB3
ZPP
b
MPP1
MPP2
MPP3
MPP4
1
2
3
4
If Zone 1 phase-phase distance element (MPP1) set
If Zone 2 phase-phase distance element (MPP2) set, not ZPP1
If Zone 3 phase-phase distance element (MPP2) set, not ZPP1 or ZPP2
If Zone 4 phase-phase distance
element (MPP4) set, not ZPP1, ZPP2, or ZPP3
ZBC
MBC1
MBC2
MBC3
MBC4
1
2
3
4
If Zone 1 BC phase-phase distance element (MBC1) set
If Zone 2 BC phase-phase distance element (MBC2) set, not ZBC1
If Zone 3 BC phase-phase distance
element (MBC3) set, not ZBC1 or ZBC2
If Zone 4 BC phase-phase distance
element (MBC4) set, not ZBC1 or ZBC2 or ZBC3
Z3P
MABC1
MABC2
MABC3
MABC4
1
2
3
4
If Zone 1 3-phase distance element (MABC1) set
If Zone 2 3-phase distance element (MABC2) set, not Z3P1
If Zone 3 3-phase distance element (MABC3) set, not Z3P1 or Z3P2
If Zone 4 3-phase distance
element (MABC4) set, not Z3P1, Z3P2, or Z3P3
ZCA
MCA1
MCA2
MCA3
MCA4
1
2
3
4
If Zone 1 CA phase-phase distance element (MCA1) set
If Zone 2 CA phase-phase distance element (MCA2) set, not ZCA1
If Zone 3 CA phase-phase distance
element (MCA3) set, not ZCA1 or ZCA2
If Zone 4 CA phase-phase distance
element (MCA4) set, not ZCA1 or ZCA2 or ZCA3
ZAG
ZAG1
ZAG2
ZAG3
ZAG4
1
2
3
4
If Zone 1 AG element (XAG1 or MAG1) set
If Zone 2 AG element (XAG2 or MAG2) set, not ZAG1
If Zone 3 AG element (XAG3 or MAG3) set, not ZAG1 or ZAG2
If Zone 4 AG element (XAG4 or
MAG4) set, not ZAG1 or ZAG2 or ZAG3
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...