B.13
Date Code 20060320
Instruction Manual
SEL-311C Relay
Firmware Upgrade Instructions
No Access Level 0 = Prompt
If no Access Level 0 = prompt appears in the terminal emulation window, one
of three things could have occurred. Refer to
to determine the best
solution:
G. Check Relay Self-Tests
The relay can display various self-test fail status messages. The
troubleshooting procedures that follow depend upon the status message the
relay displays.
Step 1. Type
ACC <Enter>
.
Step 2. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
Table B.1
Troubleshooting New Firmware Upload
Problem
Solution
The restart was successful, but
the relay data transmission rate
reverted to the rate at which the
relay was operating prior to
entering SEL
BOOT
(the rate
).
Change the computer terminal speed to match the relay
data transmission rate you recorded in
):
Step 1. From the
Call
menu, choose
Disconnect
to
terminate relay communication.
Step 2. Change the communications software settings
to the values you recorded in
.
Step 3. From the
Call
menu, choose
Connect
to rees-
tablish communication.
Step 4. Press
<Enter>
to check for the Access
Level 0 = prompt indicating that serial com-
munication is successful.
Step 5. If you get no response, proceed to
Computer Communications Speed to the
Relay on page 9
.
The restart was successful, but
the relay data transmission rate
reverted to 2400 bps (the set-
tings have been reset to
default).
Match the computer terminal speed to a relay data
transmission rate of 2400 bps:
Step 1. From the
Call
menu, choose
Disconnect
to
terminate relay communication.
Step 2. Change the communications software settings
to 2400 bps, 8 data bits, no parity, and 1 stop
bit (see
Step 3. From the
Call
menu, choose
Connect
to rees-
tablish communication.
Step 4. Press
<Enter>
to check for the Access Level
0 = prompt indicating successful serial com-
munication.
If you see a SEL
BOOT
!> prompt, type
EXI <Enter>
to exit SEL
BOOT
. Check for
the Access Level 0 = prompt.
If you see the Access Level 0 = prompt, pro-
ceed to
G. Check Relay Self-Tests on page 13
.
The restart was unsuccessful,
in which case the relay is in
SEL
BOOT
.
Reattempt to upload the new firmware (beginning at
under
Establish a High-Speed Connection on
) or contact the factory for assistance.
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...