
E.8
SEL-311C Relay
Instruction Manual
Date Code 20060320
Compressed ASCII Commands
CEVENT Command—SEL-311C
CEVENT Command—SEL-311C
Display event report in Compressed ASCII format by sending:
CEV [
n
S
x
L
y
L R C P]
(parameters in [ ] are optional)
The relay responds to the
CEV
command with the
n
th event report as shown
below. Items in bold italics will be replaced with the actual relay data.
<STX>"FID","yyyy"<CR>
"
Relay FID string
","yyyy"<CR>
"MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"FREQ","SAM/CYC_A","SAM/CYC_D","NUM_OF_CYC","EVENT",
"LOCATION","SHOT","TARGETS","IA","IB","IC","IP","IG","3I2","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,"xxxx",xxxx,xxxx,"xxxx",xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
"yyyy"<CR>
"IA","IB","IC","IP","IG","VAkV","VBkV","VCkV","VSkV","V1MEM","FREQ","VDC",
"TRIG","
Names of elements in the relay word separated by spaces
","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,z,"
HEX-ASCII Relay Word
","yyyy"<CR>
"
Analog and digital data repeated for each row of event report
"
"SETTINGS","yyyy"<CR>
"
Relay group, global, and logic settings as displayed with the showset command (surrounded by quotes
)","yyyy"<CR><ETX>
where:
n
= event number (1–43 if LER = 15; 1–25 if LER = 30; 1–13
if LER = 60; 1–4 if LER = 180; defaults to 1).
S
x
=
x
samples per cycle (4 or 16); defaults to 4.
If S
x
parameter is present, it overrides the L parameter.
L
y
=
y
cycles event report length (1–LER) for filtered event
reports, (1–LER+1) for raw event reports, defaults to LER
if not specified.
L = 16 samples per cycle; overridden by the S
x
parameter, if
present.
R = specifies raw (unfiltered) data; defaults to 16 samples per
cycle unless overridden by the S
x
parameter. Defaults to
LER + 1 cycles in length unless overridden with the L
y
parameter.
C = specifies 16 samples per cycle, LER cycle length
P = precise to synchrophasor-level accuracy for signal content
at nominal frequency. This option is available when
TSOK = logical 1.
where:
"xxxx"
= the data values corresponding to the line
labels
"yyyy"
= the 4-byte hex ASCII representation of
the checksum
"FREQ"
= the power system frequency at the trigger
instant
"SAM/CYC_A"
= the number of analog data samples per
cycle (4 or 16)
"SAM/CYC_D"
= the number of digital data samples per
cycle (4 or 16)
"NUM_OF_CYC"
= the number of cycles of data in the event
report
"EVENT"
= the event type
"LOCATION"
= the fault location
"SHOT"
= the recloser shot counter
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...