14.4
SEL-311C Relay
Instruction Manual
Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221G to SEL-311C Settings Conversion Guide
Convert SEL-221G
Primary Quantities to
SEL-311C Secondary
Quantities
All SEL-221G current settings must be converted from primary to secondary
amps to be used in the SEL-311C. Divide the SEL-221G current setting by the
current transformer ratio setting (CTR) to make the change.
SEL-221G impedance settings must be converted from percent of primary line
impedance to secondary impedance in ohms. For example, the Zone 1 distance
setting in the SEL-311C (Z1P) is calculated as
Equation 14.1
Convert SEL-221G
Relay Settings to
SEL-311C Settings
shows all the SEL-311C settings that must be entered for the relay
to perform protection similar to the SEL-221G when APP = 221G. Calculate
each SEL-311C setting from SEL-221G settings using the formula shown.
Instruction manual references are to subsection headings rather than to section
headings.
where:
Z1% = the SEL-221G distance reach setting
Z1MAG = the SEL-311C positive-sequence line impedance setting
in secondary ohms
Z1P = the SEL-311C Zone 1 reach setting in secondary ohms
Z1P
Z1%
100
------------
Z1MAG
•
=
Table 14.1
SEL-311C Settings Calculated From SEL-221G Settings
(Sheet 1 of 3)
SEL-311C
Setting
a
Calculated From SEL-221G Settings
SEL-311C Instruction
Manual Section
SEL-221G Instruction
Manual Section
RID
None
Settings Sheets for the
SEL-311C Relay
Section 3—Set n
TID
= ID
CTR
= CTR
Settings Sheets for the
SEL-311C Relay
Section 5—Choosing Current and
Potential Transformers
CTRP
= CTR
PTR
= PTR
PTRS
= PTR
Z1MAG
Settings Sheets for the
SEL-311C Relay
Section 5—Choice of
Line Impedances
Z1ANG
Section 5—Choice of Maximum
Torque Angle (MTA)
Z0MAG
Z0ANG
LL
= LL
Settings Sheets for the
SEL-311C Relay
APP
None
EFLOC
= LOCAT
Settings Sheets for the
SEL-311C Relay
Section 2—Fault Locator
ELOP
N
Y
= LOPE
= N
= Y
Loss-of-Potential Logic on
page 4.1
Section 5—Loss-of-Potential Logic
R1
2
X1
2
+
(
)
=
CTR
PTR
------------
•
Arc tan
X1
R1
-------
=
(degrees) = MTA
R0
2
X0
2
+
(
)
=
CTR
PTR
------------
•
Arc tan
X0
R0
-------
=
(degrees)
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...